Improvement of the SAG ampacity carrying level of existing 275 kV overhead line tower by using the re-conductoring approach

Mahmod, Luqman Hakim (2012) Improvement of the SAG ampacity carrying level of existing 275 kV overhead line tower by using the re-conductoring approach. Masters thesis, Universiti Tun Hussein Onn Malaysia.

[img]
Preview
Text
24p LUQMAN HAKIM MAHMOD.pdf

Download (5MB) | Preview
[img] Text (Copyright Declaration)
LUQMAN HAKIM MAHMOD COPYRIGHT DECLARATION.pdf
Restricted to Repository staff only

Download (5MB) | Request a copy
[img] Text (Full Text)
LUQMAN HAKIM MAHMOD WATERMARK.pdf
Restricted to Registered users only

Download (6MB) | Request a copy

Abstract

This project presents a methodological approach, suggestions and information in uprating the existing 275kV transmission overhead line by using the re-conductoring approach. Overhead transmission line conductors were given priority in information. Calculation regarding the maximum sag and maximum current at maximum operating temperature were the core of this project as to suggest a novel conductor available in the current market. The aim of this project is to provide more current and less sag with the new conductor proposed in comparison with the existing. In addition, the conductor will not in any way infringe the minimum safety clearance. Smart Draw, Matlab and Excel were used as a medium in the data analysis. Therefore, the apparent power of the overhead transmission line when applied with the new conductor can be calculated as to achieve the objective of this project. In Malaysia, ACSR Zebra is used as the conductor for the 275 kV L3 tower. Thus, four other conductors were chosen in order to make comparison between the maximum sag and current at maximum operating temperature. These conductors are the 3M Drake, AAC Narcissus, AAAC Greeley and ACCC 415 mm2 which have similar characteristics to the ACSR Zebra in terms of weight, maximum rated strength ratio and size. By using the calculations provided in this project, it is determined that the 3M Drake conductor is better to the ACSR Zebra in comparison of the maximum sag and the curent at maximum opertaing temperature.

Item Type: Thesis (Masters)
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering
T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK1001-1841 Production of electric energy or power. Powerplants. Central stations
Divisions: Faculty of Electrical and Electronic Engineering > Department of Electrical Engineering