Study of ozone emission and IAQ in computer laboratory

Husain, Adnan and Md. Yusof, Mohamad Zainal and Zamri Tan, Nurul Zakiah and Azizi, Baizura Aini and Leman, Abdul Mutalib (2009) Study of ozone emission and IAQ in computer laboratory. Proceedings - 6th International Symposium on Heating, Ventilating and Air Conditioning, ISHVAC 2009, 2 . pp. 973-979.

Full text not available from this repository.

Official URL: http://www.engineeringvillage2.org/controller/serv...

Abstract

This paper presents findings of study on ozone (O3) gas emission and Indoor Air Quality (IAQ) in selected computer laboratories and simulated case in a Walk-in Stability Chamber (WiSC) at University of Tun Hussein Onn Malaysia (UTHM). Measurement of O3 and IAQ parameters were carried out in two (2) computer laboratories, one consisting of 33 units of computers of age 3 years, designated as old laboratory and the other consisting of 29 units of age 1 year, designated as new laboratory. Measurements were also conducted of a simulated case in the WiSC which housed both the new and old computers. Each PC was equipped with CRT monitor. The environmental parameters measurements include the concentration of O3 gas, air temperature, carbon monoxide (CO) and carbon dioxide (CO2) gases, air velocity, ventilation rate and lighting. Questionnaires had been distributed to gauge the occupants' perception of well being and comfort, and also to evaluate the IAQ conditions and reported Sick Building Syndrome (SBS) symptoms inside both the laboratories and WiSC. Measurement was made while they were performing text typing and internet surfing. The concentration of O3 gas was measured using Aeroqual Series 500, while CO and CO2 gases were using IAQ meter. Meanwhile, the ventilation rate measurement was measured using the Automated Tracer Gas and lighting by Light Meter. Experimental data were compared with standards such as the ASHRAE Standard 62.1-2007 and U.S EPA Standard. The results of O3 concentration were between 0.015 ppm to 0.016 ppm, and 0.013 ppm in both the laboratories and WiSC respectively. Meanwhile the concentrations for CO gas were between 14.61 ppm to 15.02 ppm, and 15.01 ppm inside the WiSC. The concentration of CO2 were between 300 ppm to 725 ppm, and 558 ppm inside the WiSC. The air temperature , air velocity and lighting level were between 23 to 29°C, 0.13 m/s to 0.15 m/s, and 214 Lux to 466 Lux respectively. The result of the O3 gas concentration was within the US EPA limit and for other parameters such as air temperature, CO and CO2 gases, air velocity and lighting were with-in the ranges as prescribed by the ASHRAE Standard.

Item Type:Article
Uncontrolled Keywords:air temperature; air velocities; computer laboratory; CRT monitors; environmental parameter; EPA standards; experimental data; gas concentration; IAQ; indoor air quality; internet surfing; light meters; lighting level; Malaysia; ozone emission; sick building syndrome; stability chambers; tracer gas; ventilation rate; well being; WiSC
Subjects:T Technology > TH Building construction > TH7005-7699 Heating and ventilation. Air conditioning
Divisions:Faculty of Mechanical and Manufacturing Engineering > Department of Manufacturing and Industrial Engineering
ID Code:3132
Deposited By:En. Shahrul Md Rizal Shamshuri
Deposited On:06 Mar 2013 11:59
Last Modified:06 Mar 2013 11:59